What Kansas requires
- No business may inspect, install or service portable fire extinguishers without certification by the State Fire Marshal; the registration certificate lists the classes it may perform (Class RB for portable extinguishers), and the certification is void if the person whose qualifications it rests on leavesK.S.A. 31-133a (a), (b) ยท K.A.R. 22-10-3 (a), (b)
- Every inspection, service, recharge or installation of portable extinguishers includes a checklist or invoice, the original left with a business representative at the time, showing the business name and location, the date, the starting and ending time of the work, the name of the person who did it, the certificate holder's name, address and certificate number, the signature of a business representative, a statement that it is kept for inspection by a deputy state fire marshal or local fire inspector, and a summary of the number and types of extinguishers serviced and the type of serviceK.A.R. 22-10-19 (c)
- The checklist or invoice gives the ending time of the workK.A.R. 22-10-19 (c) (3)
- A representative of the business signs the checklist or invoiceK.A.R. 22-10-19 (c) (6)
- The certificate holder keeps a copy of each checklist for at least 24 months, open to inspection on demand by a deputy state fire marshal during normal business hoursK.A.R. 22-10-19 (c)
- A new service tag goes on each extinguisher where it is easy to inspect, with the firm's business name and address, the registration certificate class and number, the type of service, the date, "do not remove by order of the state fire marshal", the service person's signature and the type of extinguisher, all on one side; tags are about 2 1/2 inches wide and no more than 5 1/2 inches long, and no one may remove one except to perform further service, or deface or alter itK.A.R. 22-10-9
- Six-year maintenance and low-pressure hydrostatic tests are each recorded on a mylar decal no larger than 1.5 by 2.5 inches on the shell (year and month, firm, initials, and for the test, the test pressure), replacing the old one; each time a stored pressure extinguisher is opened, a white or yellow internal service label with the firm's certificate number, month and year and initials goes around the siphon tube within 1 inch of the top (carbon dioxide, halogenated, cartridge-operated dry chemical and water types are exempt)K.A.R. 22-10-19 (d) to (f)
- A Class RB holder services portable extinguishers under the Kansas Fire Prevention Code, the national standards it adopts and the manufacturer's specifications; extinguishers must carry a recognized testing laboratory's label to be sold, leased or installed, carbon tetrachloride extinguishers may not be serviced, and approved portable extinguishers are kept fully charged, operable and in their placesK.A.R. 22-10-7, 22-10-8, 22-10-15, 22-10-19 (a)
Certified businesses
A business needs State Fire Marshal certification to inspect, install or service portable extinguishers. Its registration certificate lists the classes it may do, Class RB for portables, and the certification is void if the qualified person it rests on leaves.
The checklist or invoice
Every service call ends with a checklist or invoice left with a business representative. It shows the business and location, the date, the start and end time of the work, who did it, your certificate holder's name, address and number, the representative's signature, a statement that it is kept for a deputy state fire marshal or local fire inspector, and a count of the extinguishers by type with the service done. Keep a copy for at least 24 months.
Tags and labels
A new service tag goes on each unit with the business name and address, certificate class and number, service, date, the State Fire Marshal warning, the service person's signature and the extinguisher type. Six-year maintenance and low-pressure hydrostatic tests get their own small mylar decals, and units opened for internal service get a label around the siphon tube.
From the walkthrough to a finished Kansas report
Note the time you start and finish, each unit and its service, and who signs for the business. ReportDraft counts the units by type, adds the retention statement, and leaves signature lines for you and the business representative.
Common mistakes
- No start or end time on the checklist.
- Leaving without a business representative's signature.
- Missing the count of extinguishers by type.
- Not keeping a copy for 24 months.
- A service tag without the certificate class and number.
Sources
- K.S.A. 31-133a (a), (b), checked October 15, 2026
- K.A.R. 22-10-3 (a), (b), checked October 15, 2026
- K.A.R. 22-10-19 (c), checked October 15, 2026
- K.A.R. 22-10-19 (c) (3), checked October 15, 2026
- K.A.R. 22-10-19 (c) (6), checked October 15, 2026
- K.A.R. 22-10-9, checked October 15, 2026
- K.A.R. 22-10-19 (d) to (f), checked October 15, 2026
- K.A.R. 22-10-7, 22-10-8, 22-10-15, 22-10-19 (a), checked October 15, 2026
Last reviewed October 15, 2026. Next review due January 15, 2027. This page explains published rules to help you write your report. It is not legal advice; the official text linked above governs.